VIRTUAL ELECTRICAL ENGINEERING LABORATORY

Numerical Protection of Induction Motor

Numerical relay โ€ข Phasor analysis โ€ข Fault simulation โ€ข Protection characteristics

๐Ÿ  Home

Experiment Objective

To perform numerical protection of a three-phase induction motor. The simulation calculates rated current, CT secondary current, relay pickup levels, sequence quantities and operating time for different abnormal operating conditions.

Live Measurements

Rated current โ€”
Actual current โ€”
CT secondary โ€”
โœ“ SYSTEM READY โ€” NO TRIP

Three-Phase Phasor Diagram

Voltage / Current Phasors โ€” 120ยฐ Phase Displacement
Phase A
Phase B
Phase C
Negative sequence

Numerical Protection System

Three-Phase Motor Feeder THREE-PHASE SUPPLY BREAKER CTs NUMERICAL RELAY 49 โ€ข 50/51 โ€ข 50N/51N โ€ข 46 HEALTHY INDUCTION MOTOR CT secondary measurement EARTH

Numerical Calculations

1. Rated Motor Current

IN = P 3 ยทV ยทฮท ยทcosฯ†
โ€”

2. CT Secondary Current

Is = Ip ร— CTs CTp
โ€”

3. Thermal Pickup โ€” 49

IOL = K100 ร— IN
โ€”

4. Overcurrent Pickup โ€” 50/51

IOC = K100 ร— IN
โ€”

5. Earth Fault Pickup โ€” 50N/51N

IEF = K100 ร— IN
โ€”

6. Negative Sequence Pickup โ€” 46

I2 = K100 ร— IN
โ€”

Inverse-Time Relay Characteristic

IEC-style inverse characteristic
Inverse characteristic
Pickup
Operating point

Three-Phase Current Waveform

Phase currents with 120ยฐ displacement
IA
IB
IC

Protection Pickup Comparison

Protection Decision

Element Pickup Measured Decision
49 โ€” โ€” โ€”
50/51 โ€” โ€” โ€”
50N/51N โ€” โ€” โ€”
46 โ€” โ€” โ€”

Adjust the relay settings and run the simulation.