1. Experiment objective
START HEREWhat are we trying to understand?
A generator normally converts mechanical energy into electrical energy and supplies real power to the grid. If the mechanical input to the generator is lost while the generator remains connected to the grid, the direction of real power can reverse.
Normal generating condition
Reverse power / motoring
The purpose of the reverse-power relay is to detect this condition and disconnect the generator before prolonged motoring causes undesirable operation of the generating unit.
2. Principle of reverse-power protection
THEORYFor a balanced three-phase system, real power can be represented by:
The important quantity for this experiment is not only the magnitude of power, but also its direction.
| Power | Direction | Generator condition | Relay interpretation |
|---|---|---|---|
| +P | Generator → Grid | Generating | Normal |
| 0 | No real-power transfer | Transition | No reverse-power operation |
| −P | Grid → Generator | Motoring | Reverse-power region |
3. What happens physically?
CONCEPT MAPsupplies
input falls
zero
reverses
times
trips
Temporary disturbances and transient power reversals should not necessarily cause an immediate generator trip. The relay can therefore be coordinated with an intentional operating delay.
4. Generator protection single-line diagram
PUBLICATION-STYLE SVG5. Live relay indication
LIVE6. Guided demonstration — from generating to motoring
WATCH THE SEQUENCEThe demonstration automatically reduces the simulated mechanical input. Watch the power flow change from export to import and observe when relay 32 starts timing.
7. Virtual relay test set
EXPERIMENT8. Live engineering calculation
MATHML9. Reverse-power operating characteristic
GRAPH10. Power versus time
OSCILLOGRAPHThe red dashed line represents the reverse-power pickup threshold. A trip occurs only when the reverse-power condition remains beyond pickup for the selected time delay.
11. Directional power visualization
SVG12. Observation table
RECORD| Parameter | Observed value | Meaning |
|---|---|---|
| Line voltage | 11.0 kV | Generator terminal voltage |
| Line current | 131.2 A | Measured current |
| Power factor | 0.99 | Phase relationship |
| Real power | +2.47 MW | Direction of real-power flow |
| Pickup setting | −0.25 MW | Reverse-power threshold |
| Relay state | STABLE | Present protection condition |
| Operating time | 0.00 s | Relay timing |
13. Think while performing the experiment
GUIDED LEARNINGNegative power means power is flowing toward the generator.
Negative power beyond the pickup setting for the required time causes the simulated relay to trip.
14. What should you understand after this experiment?
A reverse-power relay protects a generator against sustained reverse real-power flow. The relay determines the direction of real power, compares the measured reverse power with its pickup setting, applies the specified time delay, and then issues a trip command when the operating condition is satisfied.