Radial Feeder Protection Schematic
Primary pickup
400 A
Fault current
2400 A
PSM
6.00
Trip time
1.002 s
Numerical IDMT Relay Calculations
CT Secondary Fault Current
Plug Setting Multiplier
IDMT Characteristic Equation
IEC Standard Inverse characteristic:
\(k=0.14,\ \alpha=0.02\)
Numerical Operating-Time Calculation
IDMT Time–Current Characteristic
Relay characteristic
Operating point
Fault Current Waveform
Current waveform
Fault region
Operating Point & Results
| Parameter | Value | Engineering interpretation |
|---|---|---|
| System voltage | 11 kV | Nominal feeder voltage |
| CT ratio | 400/1 A | Current transformation ratio |
| Primary pickup current | 400 A | Pickup threshold referred to primary |
| Fault current | 2400 A | Simulated primary fault current |
| Relay secondary current | 6.00 A | Current measured by numerical relay |
| Plug Setting Multiplier | 6.00 | Fault current divided by pickup current |
| Time Multiplier Setting | 0.100 | Controls relay operating time |
| Calculated operating time | 1.002 s | IDMT operating time for selected characteristic |
Working Principle
An inverse definite minimum time overcurrent relay operates when the measured current exceeds the preset pickup current. The relay operating time decreases as the magnitude of fault current increases. For a radial feeder, this inverse characteristic assists in obtaining selective coordination between upstream and downstream protection.
| Characteristic | Equation | ||
|---|---|---|---|
| IEC Standard Inverse | |||
| IEC Very Inverse | |||
| IEC Extremely Inverse |